Report: CVE-2026-3611 - Honeywell IQ4x BMS Controller Missing authentication for critical function
CVE ID :CVE-2026-3611 Published : March 12, 2026, 9:16 p.m. | 49 minutes ago Description :The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration. Severity: 10.0 | CRITICAL Visit the link for more details, such as CVSS details, affected products, timeline, and more...